General Description
Room Size:
- 40 ft long, 8 feet wide
- 9 feet high. 320 square feet of floor space
- total of 2880 cubic feet
Insulation:
- R15 walls
- R22 ceiling
- Vapour barrier inside insulation on all walls and ceiling
Entry:
- light locked entrance from inside of building
- man door to exterior and loading dock
Lighting: 3 x 40 Watt red lights
Ventilation:
- 10?” diameter squirrel cage fan
- 2300 cubic feet per minute at ¼” back-pressure (Dayton Blower: 1725 rpm, 208 Volts, 7.0 Amps, 1 phase)
- intake port: 12” diameter galvanized duct, painted flat black inside
- circulation duct: 30 feet long ,12” reinforced polyethylene duct with perforations equal to the area of the intake port.
- thermostat mounted beside intake with sensor mounted outside
- fan pressurizes room and forces heavy CO2 laden air out wooden floor ducts (8”x8”) and then out 8” galvanized duct. This metal duct is painted flat black inside.
Refrigeration
Compressor: Bohn Refrigeration Model DBH3H2EC23P: 230 Volts, 17 Amps, 3 horsepower, 1 phase
Condenser: Bohn Refrigeration Model MAB365OF: 115 Volts, 12 Amps, ¼ horsepower; 3 fans (each: ¼ horsepower, 1 phase, 4.0 Amps)
Heating:
- 2x Q Mark heaters – Marley Electric Co. Model MUH03-21
- 12 Amps each
- 208/230 Volts each
- 2600 Watts each
- 1 phase
- 8” fan on each heater (0.25 Amps each)
Controls:
- electrical heat thermostat
- cooling thermostat
- fan time clock
- fan override switch
- electrical heat disconnect (heater #1)
- electrical heat disconnect (heater #2)
- electrical heat relay
- ventilation fan relay
- 10 Amp control fuse
- fan disconnect
- intake fan thermostat with sensor mounted inside and outside
Operation
Ventilation: Timer turns on fan every 30 minutes. All air in room is exhausted under pressure in 1.5 minutes, then fan shuts off.
Temperature Control
If outside air is cooler than desired inside temperature:
- thermostat with inside and outside temperature sensors turns on fan to cool room with outside air
- fan still exhausts all air every 30 minutes
If outside air is warmer than desired inside temperature:
- air conditioning system cools and circulates inside air
- fan still exhausts all air every 30 minutes
Alarm System
Thermostatically controlled alarm is activated if room temperature changes ±5?C from desired temperature, due to power outage or equipment failure.
Installations
Cook and Beals Inc. (Loup City, Nebraska, USA) supplied and installed all equipment with help from F.M. Electric Ltd. and Share-Temp Refrigeration, both of Guelph, Ontario.
NOTE: The operating temperature would be 7-9?C (45-48?F) for single story colonies with about 3 pounds of bees. Appropriate temperatures for smaller or larger colonies would be higher or lower, respectively.
Download the Indoor Overwintering Room specifications: OW-room-specs